All (1) the fans circulating within the European community of power between 125 W and 500 kW from January 2013 will be in accordance with Regulation (EU) N.327/2011 Commission. The efficiency of the fans to meet the European standards, must reach a minimum level. The legislation requires that at least the point of maximum efficiency is greater than or equal to the limits, these limits are fixed with two dates in January 2013 and January 2015. The Regulation states that the verification of compliance with the same regulations can be achieved either through measures that calculations depending on the configuration of the fan.

Type of fan Measurement category Efficiency class Power range P [kW] Energy efficiency target Efficiency (N) 2013 Efficiency (N) 2015
Centrifugal fan with forward curved blades A, C

Static η e = η sta 

0,125 < P ≤ 10 
η target = 2,74* In (P) - 6,33 + N  37  44 
10 ≤ P ≤ 500
η target = 0,78* In (P) - 1,88 + N
B, D

Total η e = η tot

0,125 < P ≤ 10
η target = 2,74* In (P) - 6,33 + N 42 49
10 ≤ P ≤ 500
η target = 0,78* In (P) - 1,88 + N

ERP 

 

 

CMC Srl proof ventilation fans in our laboratory according to ISO 5801 and AMCA 210-07 legislation, the outcome of the tests is achieved compliance with ErP can measure the air flow, the pressure and the electrical power input in the motor. In the assessment of compliance must be taken into consideration all the parts are functionally connected to the fan.

  • Fan - Fan with Screw
  • Electric Motor
  • Transmission (if any)
  • Speed Regulator (if any)

 

 

   

Tipe of Fan Method of verification    
Direct drive fan CMC Ventilazione - measure ready for use
Direct drive fan with speed regulator η target ≥ (ηe/Cc) used after verification
Belt drive

Supplied with drive motor CMC Ventilazione - measure ready for use
Supplied without drive motor (2)
η target ≥ η r * η m * η t * Cm
used after verification
Belt drive with speed regulator

Supplied with drive motor η target ≥ (ηe/Cc) used after verification
Supplied without drive motor (2) η target ≥ η r * η m * η t * Cm * Cc used after verification

 

 Description

Symbol

Calculation/measurement

Unit of measure

Aeraulic power (total)

Pu(s)tot
= Q * Pt
W

Power aeraulic (static)

Pu(s)sta
= Q * Ps
W

Overall efficiency

ηe
= Pu(s) / Pe
-

Total efficiency 

ηtot
= Pu(s)tot / Pe
-

Static efficiency

ηsta
= Pu(s)sta / Pe
-

Efficiency of the fan 

ηr
= Pu(s) / Pa
-
Motor efficiency
ηm
 
engine in accordance with regulation (EU)
No 640/2009
 
nominal efficiency of the motor
-
 
engine in accordance with regulation (EU) No 640/2009 or not provided
 
Pe < 0,75 kW 
= 0,1462 * ln(Pe) + 0,8381
-
Pe ≥ 0,75 kW 
= 0,000278*(ln(Pe)3) –
0,019247*(ln(Pe)2) +
0,104395*(Pe)+0,809761
-
Efficiency of the traction device
ηt
 
direct transmission
 
= 1,0
 
Device low efficiency
Pa ≤ 1,0 kW 
= 0,96
-
1 kW < Pa < 5,0 kW 
= 0,0175 * Pa + 0,8725
-
Pa ≥ 5,0 kW 
= 0, 89
-
High device efficiency
Pa ≤ 1,0 kW 
= 0,98
-
1 kW < Pa < 5,0 kW 
= 0,01 * Pa + 0,93
-
Pa ≥ 5,0 kW 
= 0,94
-

Factor compensation for commissioning together (matching) of components

Cm
= 0,9
-

Factor compensation partial load

Cc
Ped < 5 kW 
= -0,03 * ln(Ped) + 1,088
-
Ped ≥ 5 kW 
= 1,04
-
Flow
Q
CMC Ventilazione - measure 
m3/s
Total pressure
Pt
CMC Ventilazione - measure 
Pa
Static pressure
Ps
CMC Ventilazione - measure 
Pa
Electrical power
Pe
CMC Ventilazione - measure 
W

The fan shaft power

P
CMC Ventilazione - measure 
W

Power input the drive 

Ped
measure 
W


Note:

(1) Except for the fans which is subject of the exemption Article 1 point 2 and 3 Regulation (EU) N.327/2011 Commission.
“… Article 1 …

Step 2:
This Regulation does not apply to fans integrated in:
I) products with a single electric motor of 3 kW or less where the fan is fixed on the same shaft used to move the main functionality;
II) tumble dryer and washing machines with built-in electrical power input ≤ 3 kW;
III) hoods electrical power input maximum total <280 W due to the fans.


Step 3:
This Regulation does not apply to fans which are:
a) designed specifically to operate in potentially explosive atmospheres as defined in Directive 94/9/EC of the European Parliament and of the Council (1);
b) designed to operate only in cases of emergency, for short periods, in relation to fire safety regulations laid down in Directive 89/106/EC of the Council (2);
c) specifically designed to work:
i) a) when the operating temperature of the circulating gas above 100 ° C;
b) when the ambient temperature of the motor operating the fan action that, if placed outside of the gas flow, exceeds 65 ° C;
ii) when the annual average temperature of the circulating gas and / or the ambient temperature of the engine, if placed outside of the gas flow, is less than - 40 ° C;
iii) with a supply voltage> 1 000 V AC or> 1 500 V DC;
iv) in a toxic environment, highly corrosive or flammable gases or in environments with abrasive substances;
d) placed on the market before 1 January 2015 as a replacement for identical fans integrated in products that have been placed on the market before 1 January 2013. …”

(2) Ventilation CMC offers its customers the ability to carry out tests to verify the correspondence to Council Regulation (EU) N.327/2011 Commission, the fan drive motors and other components in use by customers.

DAIN

DA-IN

SAPPE

SAPPE_PLT60-

CBT

DARE

dare

DTA

DTA

MCK

mck

DAREB

dareb

RFB

dare

VDI

VDI

SAREB

sareb

AX

AX

MCT 400

bbf

ErP "Energy related Products"

ERP


All (1) the fans circulating within the European community of power between 125 W and 500 kW from January 2013 will be in accordance with Regulation (EU) N.327/2011 Commission. The efficiency of the fans to meet the European standards, must reach a minimum level.

read more »

Laboratory tests

Test di laboratorio


Design and supply of laboratories for testing fans and control of air flow. Laboratories comply with AMCA 210/ISO 5801.

read more »